BKC Series Explosion Proof Window Air Conditioners 5400W 7000W For Zone 2

BKC Series Explosion Proof Window Air Conditioners 5400W 7000W For Zone 2
Download Download Brochure
Data
Type BKC-50/220 BKC-70/220
Cooling capacity W 5400 7000
BTU 18000 24000
Rated voltage/Frequency (V/Hz) 220~240/50 220~240/50
Input power (P) 2P 3P
Cooling input power (W) 2750 3770
Rated current (A) 12.8 17.4
Application areas (m²) 22~32 30~40
Sound level (dB) Indoor unit ≤53 ≤57
Outdoor unit ≤60 ≤63
Outline dimensions (L x W x H) (mm) 730 x 680 x 450 730 x 680 x 450
Weight (kg) 50 55
warromLogo
Engineering Diagram
Specification
Global (IECEx) IECEx CQM 11.0021X
Gas Ex d nC IIB T4 Gc
Europe (ATEX) LCIE 11 ATEX 1002X
Gas Ex II 3 G Ex d nC IIB T4 Gc
Certificates IECEx; ATEX; CU-TR
Conformity to standards EN;IEC